Model HCP-E(SCI) is a Manual Call Point with integral short-circuit isolator, which is fully
compatible with Hochiki’s ESP analogue addressable protocol. The unit incorporates a bi-
coloured LED, which can be selected as pulsing/non-pulsing*1 for communications polling and
is continuously lit when the HCP-E(SCI) is operated – in these two states the LED will show
red. The LED will show amber when a short-circuit is present but will switch to red if the unit
is activated. The unit operates by pressing the EN54 compliant non-frangible (plastic)
element and produces a high level ESP interrupt. A built in test function initiated by the
control panel ensures the integrity of the device at all times and the device can be tested by
insertion of a test key in the underside of the unit. Two terminal blocks are provided for easy
connection to the loop wiring.
The unit is addressed using the TCH-B100 Hand Held Programmer for quick and reliable
addressing. The unit can be flush mounted as supplied. For surface fixing a suitable back box
such as the SR MOUNTING BOX is required (sold separately). An optional glass element is
also available.